Flow sensor Y19SENS01

Flow sensor Y19SENS01

The CMC nv datasheet for flow sensors Y19SENS01 and Y21SENS01 can be accessed through the following link:

Factsheet Flow sensors Y19SENS01 and Y21SENS01

Info
This sensor type does not support the "display" feature, and does not require any configurations.

Quick Guide: Finding Your Flow Range

The table in the manual lists the maximum flow for each pipe size at 0 bar pressure. To find the maximum flow for your operating pressure, use this formula:

Your Max Flow = (Table Value) × (Your Pressure + 1)

Example for a 1-inch pipe at 7 bar:
  1. From the table, a 1" pipe has a max flow of 4.06 m³/min at 0 bar.
  2. Your pressure factor is 7 + 1 = 8.
  3. Your Max Flow = 4.06 × 8 = 32.48 m³/min.